Example 5: Data Channel Concatenation
In this example, data on a single channel only is transferred from end to end, across
unsynchronised X21 links.
Set Aggregate Direction for all units to X21 port. Transmit and Receive data is
presented at all ports. Only possible on a well disciplined system where only on
terminal transmits at once. This configuration allows both X21 links to run
unsynchronised.
Each link runs at its own clock speed. The data is transferred from B1 to B2 at V24
level by effectively being re-transmitted from the SCADA equipment.
DIP Switch Settings for all units
8 7 6 5 4 3 2 1
SW1 * * * * * * * *
SW2 0 1 0 0 1 0 0 1
SW3 * * * * * * * *
SW4 * * * * * * * *
SW5 0 0 0 0 0 0 0 1
SW6 0 0 0 0 * * 1 *
* indicates setting not applicable to this setup
If a Westica radio is to be used, these are configured as detailed in Section 7.6
Figure 7-1 of the Westica manual. Radio 1 is configured as Int Master (DCE), Radio
2 at C1 end is configured as Slave (DCE).
The Interconnection cable at each end is straight X21, as Cable Y in Example 3.
Substation A Substation B Substation C
X21
C1 B2B1A2
V24
Port 2
V24
Port 2
V24
Port 2
V24
Port 2
Aggregate channels: V24 port 2 on each unit is allocated to channel B, baud rate 2400
Example installation – SCADA network
SCADA Equipment